Home > Equipment > Object Terminals > AS006K
Object Terminal “Antaeus” AS006K and AS006KD
“Drozd”
Being a part of transmitting system “Antaeus” this equipment
is designed for central guard of domestic/industrial premises and
prevention of infiltration and fire. This goal is achieved by
monitoring of system loops with installed alarm/fire annunciators
and by sending alarm messages to the central surveillance console.
The messages are sent through one or two telephone lines. The
data format if ADEMCO ID Contact.
OTs, providing guard of nearby objects located in one
building, are united in one logical group transmitting messages to
each other. Such a solution much increases the reliability and the
“vitality” of the security system. Besides when uniting OTs into one
local groups certain units of such a group may be used for guarding
objects lacking a telephone.
The interacting of OTs within one local group does not
require additional channels. The exchange of information is done
through the electrical network (220V) by specially coded signals.
In case of alarm/fire annunciator’s response, pressing of
help button and other events OT sends a message to CSC on the
telephone. If OT cannot make an alarm call by itself (because of
deliberate/accidental line fault or equipment break) the message is
sent through electrical network to another OT within the group which
forwards it to the CSC. Moreover, CSC will receive an alarm message
about OT failure even if it fails completely.
The characteristics of the system loops:
Source voltage |
12V |
Nominal value of loop resistance
- special mode |
2.2 kOhm
12 kOhm |
Lowest operating threshold |
1.4 kOhm |
Highest operating threshold
- special
mode |
3.4 kOhm
15 kOhm |
Hump resistance of loop wires |
0.5 kOhm |
Terminal resistance of loop leakage |
20 kOhm |
Operating time in normal mode |
400 ms |
Operating time in fast mode |
60 ms |
The mode of each zone is set individually when
programming the equipment. Each zone may be programmed as buffer
zone, fire zone, zone of sending emergency calls or control zone.
Connection of any type of annunciator is allowable including
loop-powered.
OT supports programmable delay (0…255s) at the input/output.
OT supports up to 9 different user passwords and 9 remote
controls’ codes (AS006K)/9 electronic keys’ codes (AS006KD). One can
also use password for enforced disengaging of alarm system, in this
case CSC receives a discrete message.
Mode and status indication are achieved by connecting remote
indicator (light-emitting diode) to OT. Besides it’s possible to
connect a light-indicator or sound annunciator with more capacity to
the installed relay. OT has got a flexible multifunctional relay.
One can also set a mode for monitoring telephone line (with
the help of transmitting system “Phobos”).
OT is powered through electric network (220V), the maximum
wattage is 10 W. OT has got a backup power supply (a battery), OT
receives a message from the CSC if primary power supply fails. OT
has got a 12 V outlet powering external devices (light/sound
annunciators) the total current of which must not exceed 250 mA.
OT must be run at a temperature +1 - +40C, the relative
humidity is up to 90% at the temperature 25% (hardness group 4
according to GOST 15150 69). The maximum OT size if 154x111x45mm,
maximum weight is 0.5 kg.
The configuration of object terminal
“Antaeus” AS006K and AS006KD “Drozd”:
Object terminal “Antaeus” AS006K and AS006KD – 1
Light-emitting diode ŔË307Á ŔŔ0.336.076ŇÓ – 1
Resistor Ń2-33-0.25 2.2kOhm ÎĆ0.467.173ŇÓ – 4
Remote control (AS006K) or electronic key (AS006KD) – 2
Operation manual – 1
Package – 1
|